Power Supply

Power Supply

This series includes the AD25002S and AD25003S models, featuring a rugged and high-power-density design, specifically developed to meet space-saving requirements and industrial applications. All models come with built-in dry contact alarm signals and O-ring diodes, supporting redundant system configurations, and are equipped with overvoltage protection, overload protection, and short-circuit protection to ensure reliable operation. The design is flexible, allowing installation on T.35 rails or easily mounted on walls using the included mounting brackets. All models comply with RoHS standards, carry the CE mark, and are UL508 certified.

Product Features

1. Innovative industrial-grade rail-mounted power supply design
2. Air natural convection cooling
3. Overvoltage protection
4. Overload protection
5. Short circuit protection
6. Rail-mounted/clip-lock mounting for easy installation
7. Optional dry contact alarm signal/backup functionality
8. High power density
9. High reliability
10. Compact size, high efficiency, cost-effective
11. Complies with RoHS/UL/CE standards
12. 3-year warranty
13. Operating Environment
14. Operating temperature: -40°C to 50°C
15. Operating humidity: 5%-95% relative humidity, non-condensing

Downloads

Specifications

General specifications

project

illustrate

Switching frequency

85kHz

Isolation Voltage

Input-Output3000VAC / 4242VDC
Input-FG1500VAC / 2121VDC
Output-FG500VAC / 710VDC

Isolation Resistance

100MΩ (when Input-Output @500VDC)

Operating Temperature

-40°C ~ +40°C (Ambient)

Derating

Output is reduced by 2.5% per °C for every 40°C exceeded, up to a maximum of 60°C

Storage Temperature

-40°C ~ +85°C

Relative Humidity

5% ~ 95% RH (non-condensing)

Temperature Coefficient

±0.04% change in output voltage per °C

Mean time between failures (MTBF).

60,000 hours per MIL-HDBK-217F, 25°C GB

Altitude During Operation

2000 meters

Installation Position

vertical

Vibration-resistant design

Random vibration, 10~500Hz (triaxial)

Enter the specifications

project

illustrate

Input Voltage

115/230VAC ±15% optional

Input Frequency

47~63Hz

Inrush Current Cold Start

22A @ 115VAC 44A @ 230VAC

Rated Input Current

Max 10A @ Vi=110120VAC<br > Max 6A @ Vi=200240VAC

Leakage Current

Input-output0.25mAInput-FG3.5mA@250VAC

Output specifications

project

illustrate

Output Voltage Accuracy

±1%

Minimum Load

0%

Line Regulation

±1% (low to high)

Load Regulation

±2% (20% to 100% load)

Voltage trim range

±10%

Rated Continuous Loading

21A @ 24VDC
10.5A @ 48VDC

Hold-up Time

20ms minimum (@230VAC full load)

Turn On Time

1300ms

Rise Time

15ms

Fall Time

35ms

  • Model:AD2500S Series