Power Supply

Power Supply

This series includes the AD1500-24S and AD1500-48S models, featuring a rugged and high-power-density design, specifically developed to meet space-saving requirements and industrial applications. All models come with built-in dry contact alarm signals and O-ring diodes, supporting redundant system configurations, and are equipped with overvoltage protection, overload protection, and short-circuit protection to ensure reliable operation. The design is flexible, allowing installation on T.35 rails or easily mounted on walls using the included mounting brackets. All models comply with RoHS standards, carry the CE mark, and are UL508 certified.

Product Features

1. Innovative industrial-grade rail-mounted power supply design
2. Natural convection air cooling
3. Overvoltage protection
4. Overload protection
5. Short-circuit protection
6. Rail-mounted/clip-lock mounting for secure installation
7. Optional dry contact alarm signal/backup functionality
8. High power density
9. High reliability
10. Compact size, high efficiency, cost-effective
11. Complies with RoHS/UL/CE standards
12. 3-year warranty
13. Operating Environment
14. Operating temperature: -40°C to 50°C
15. Operating humidity: 5%-95% relative humidity, non-condensing

Downloads

Specifications

General specifications

project

specification

Switching frequency

85kHz

Isolation Voltage

Input-Output3000VAC / 4242VDC
Input-FG1500VAC / 2121VDC
Output-FG500VAC / 710VDC

Insulation resistance

100MΩ (when Input-Output @500VDC)

as temperature

-40°C ~ +40°C (Ambient)

Derating

Decrease output power by 2.5% per °C to 60°C for every 40°C exceeded

Storage temperature

-40°C ~ +85°C

relative humidity

5% ~ 95% RH (non-condensing)

Temperature coefficient

±0.04% change in output voltage per °C

Mean time between failures (MTBF).

60,000 hours per MIL-HDBK-217F, 25°C GB

Maximum work height

2000 meters

Installation:

vertical

Vibration resistance

Random vibration 10~500Hz (3 axes)

Enter the specifications

project

specification

Input voltage

115/230VAC ±15% (optional)

Enter the frequency

47~63Hz

Inrush current (cold start)

22A @ 115VAC 44A @ 230VAC

Rated input current

10A max. (Vi=115VAC) and
 6A max. (Vi=230VAC).

Leakage current

Input-Output0.25mAInput-FG3.5mAVi=250VAC

Output specifications

project

specification

Output voltage accuracy

±1%

Minimum load

0%

Line Regulation

±1% (low to high input voltage measurement)

Load Regulation

±1% (from 20% to 100% rated load, 230VAC)

Voltage trimming range

±10%

Rated continuous output current

21A @ 24VDC10.5A @ 48VDC

Hold-up Time

20ms (full load, 230VAC).

Turn On Time

1300ms

Rise Time

15ms

Fall Time

35ms

  • Model:AD1500S Series