Battery Charger

Battery Charger

The AD2120CF series is a DC uninterruptible power supply (DC UPS) that combines an AC-DC switch-mode power supply, backup control circuitry, and a battery charger to provide stable, uninterrupted DC power. With a wide AC input range and TS35 DIN rail installation design, it is ideal for applications such as security monitoring systems, telecom systems, and environmental monitoring systems. It features built-in AC power failure dry contact alarm signals and low battery voltage dry contact alarm signals for real-time monitoring of operation. Additionally, the AD2120CF series includes comprehensive protection mechanisms such as overload protection, short circuit protection, overcurrent protection, reverse polarity protection, and low battery voltage shutdown, ensuring safe and stable system operation, especially in applications requiring long-term stable power supply.

Product Features

1. High power density
2. Natural convection cooling design
3. Supports DIN rail and wall-mounted installation
4. Built-in overvoltage protection
5. Equipped with overload protection and short circuit protection
6. Complies with RoHS standards
7. 3-year quality warranty
8. Operating Environment:
9. Operating temperature: -40°C to 50°C
10. Operating humidity: Non-condensing, 5% to 95% relative humidity

Downloads

Specifications

General specifications

project

specification

Switching frequency

85kHz

Isolation voltage

Input-Output: 3000VAC/4242VDC
 Input-Ground: 1500VAC/2121VDC
 Output-Ground: 500VAC/ 710VDC

Insulation resistance

100 megaohms when the input and output are added to 500 volts DC

as temperature

-40°C to +40°C ambient temperature

Conditions for derating

Derating 2.5% for every 1°C increase from 50°C to 60°C

Storage temperature

-40°C to +85°C

relative humidity

5%~95%, non-condensing

Temperature coefficient

The output voltage changes by ±0.04% per °C

Mean time between failures

Minimum 60,000 hours (25°C per MIL-HDBK-217F).

Enter the specifications

project

specification

Input voltage

100~240 volts AC / 120~370 volts DC

Enter the frequency

47~63 Hz

Starting Surge Current (Cold Start)

115 volts AC: 22 amps; 230 volts AC: 44 amps

Rated input current

3.5 amps max (voltage 100~240 VAC)

Leakage current

Input-output: 0.25 mA, input-ground: 3.5 mA

Output specifications

project

specification

Output voltage accuracy

±1%

Minimum load

0%

Voltage Stability (Linear)

±1% from low to high input voltage measurements

Load stability

±3% from 20% to 100% rated load (230 volts AC input)

Voltage trimming range

±10%

Rated continuous output current

According to the product model table

Hold time

Minimum 20 ms (230 volts AC input, full load condition)

Boot

1300 milliseconds

Rise time

13 ms

Drop time

25 ms