Power Supply

Power Supply

This series includes the AD1040-05F, AD1048-12F, AD1048-24F, and AD1048-48F models, featuring a rugged and high-power-density design, specifically developed to meet space-saving requirements and industrial applications. All models come with built-in dry contact alarm signals and O-ring diodes, supporting redundant system configurations, and are equipped with overvoltage protection, overload protection, and short-circuit protection to ensure reliable operation. The design is flexible, allowing installation on T.35 rails or easily mounted on walls using the included mounting brackets. All models comply with RoHS standards, carry the CE mark, and are UL508 certified.

Product Features

1. Innovative design of industrial-grade rail-mounted power supply
2. Natural convection air cooling
3. Overvoltage protection
4. Overload protection
5. Short-circuit protection
6. Rail-mounted/clip-lock mounting for secure installation
7. Optional dry contact alarm signals/backup functionality
8. High power density
9. High reliability
10. Compact size, high efficiency, cost-effective
11. Complies with RoHS/UL/CE standards
12. 3-year warranty
13. Operating Environment
14. Operating temperature: -40°C to 50°C
15. Operating humidity: 5%-95% relative humidity, non-condensing

Downloads

Specifications

General specifications

project

specification

Switching frequency

70kHz

Isolation Voltage

Input-Output3000VAC / 4242VDC
Input-FG1500VAC / 2121VDC
Output-FG500VAC / 710VDC

Insulation resistance

100MΩ(Input-Output @500VDC

as temperature

-40°C ~ +50°C (Ambient)

Derating

Above 50°C, reduce the load capacity by 2.5% per degree to 70°C

Storage temperature

-40°C ~ +85°C

relative humidity

5% ~ 95% RH (non-condensing)

Temperature coefficient

±0.04% change in output voltage per °C

Mean time between failures (MTBF).

60,000 hours per MIL-HDBK-217F, 25°C GB

Maximum operating height

2000 meters

Installation:

vertical

Vibration resistance

Random vibration, frequency range 10~500Hz, triaxial

Enter the specifications

project

specification

Input voltage

100240VAC / 120370VDC

Enter the frequency

47~63Hz

Inrush current (cold start)

22A / 115VAC 44A / 230VAC

Rated input current

Max 1A (input 100~240VAC)

Leakage current

Input-Output0.25mAInput-FG3.5mAVi=250VAC

Output specifications

project

specification

Output voltage accuracy

±1%

Minimum load

0%

Line Regulation

±0.5% (measured from low to high pressure)

Load Regulation

±0.5% (from 20% to 100% load rating, 230VAC input)

Voltage trimming range

±10% (minimum)

Rated continuous output current

8A@5VDC4A@12VDC2A@24VDC1A@48VDC

Hold Time

35ms (full load, 230VAC).

Turn On Time

1200ms

Rise Time

10ms

Fall Time

30ms

  • Model:AD1048F Series